The Schneider Electric Acti 9 A9XAH257 is a cutable comb busbar designed for efficiently connecting multiple modular devices in single-phase electrical installations. It's ideal for electricians and installers seeking a reliable and adaptable solution for power distribution, offering a neat and organized wiring method. A key benefit is its customizability through cutting to precise lengths, though it requires careful planning to ensure compatibility with specific device types and correct phase configuration.
| Model Part Number | A9XAH257 |
|---|---|
| Brand | Schneider Electric |
The A9XAH257 has 57 modular spacings and a 45mm pitch, allowing it to connect up to 22 two-pole devices.
No, this busbar is specifically designed for 2-pole single-phase systems.
The rated permanent current (Iu) for this busbar is 100A.
The rated operational voltage (Ue) is 415V AC, and the rated insulation voltage (Ui) is 500V AC.
Always ensure the main power supply to the distribution board is switched off and locked out before installation. Follow standard electrical safety procedures and ensure the busbar is fully seated and connections are secure.
While it might physically fit, Schneider Electric strongly recommends using this busbar only with the specified compatible Schneider Electric devices (iC60, iID, ISW-NA, iK60, iID K, ISW) to guarantee performance, safety, and compliance.
Yes, this product is marked as a 'Better World Product' and is verified as 'Green Premium', indicating its environmental performance and compliance with regulations like RoHS.
Ensure the devices are compatible Schneider Electric models (iC60, iID, ISW-NA, iK60, iID K, ISW) and that the busbar has been cut cleanly and to the correct length for the 45mm pitch.
Re-seat the busbar ensuring it is fully engaged in the device terminals. Check for any debris or damage on the busbar or device connection points.
Immediately disconnect power. Inspect the busbar and device terminals for damage or excessive resistance. Ensure the busbar is rated for the load and properly seated. If overheating persists, replace the busbar and/or affected devices.
Use a sharp, appropriate cutting tool designed for electrical busbars. Ensure the busbar is properly supported during cutting.
Setup:
Compatibility:
This busbar is specifically designed for use with:
Verify the specific model numbers of your devices to ensure compatibility before installation. The busbar features a 45mm pitch, suitable for devices with standard modular spacings.
Care: